XLPE Insulated Power Cable

Bookmark Print Contact Chat Application:This type of XLPE Insulated Power Cable is used for power transmission and distribution line with voltage rated at 35kV and below. In comparison with PVC Insulated Power Cable,  XLPE power cable boasts not only characteristics of excellent electricity, mechanism, heat and aging-resistant, environment stress-resistant and chemical corrosion-resistant, but also simple structure, light weight, no restriction by laying drop, and high temperature allowance for long-term working.
XLPE Insulated Power Cable

0.6/1kV 4-core XLPE Insulated Power Cable

XLPE Insulated Cable
0.6/1kV 4+1-core XLPE Insulated Power Cable

XLPE Cable
26/35(40.5)kV 3-core XLPE Insulated, Steel tape Armored, PVC Sheath Power Cable


XLPE Insulated Power Cable Standard:
 
1) Equivalent IEC 60502-1, GB/T12706.1;
Rated Voltage 1 kV (Um=1.2kV) and 3 kV (Um=3.6kV) Power Cable.
 
2) Equivalent IEC 60502-2, GB/T12706.2;
  Rated Voltage 6 kV (Um=7.2kV) to 30 kV (Um=36kV) Power Cable.
 
3) Voltage Grade Overstep IEC60502, GB/T12706.3;
  Rated Voltage 35 kV (Um=40.5kV) Power Cable

Operating Features:
 
1The maximum conductor operating temperature:  90
During short circuit (lasting less than 5 seconds) the maximum temperature of the cable conductor shall not be above 250℃;
Environment temperature should be no lower than 0℃ for laying the cable.

2Bending Radius of the Cable:
Single Core Cable: Non Armored Cable 20D,  Armored Cable 15D;
Cores Cable: Non Armored Cable 15D,  Armored Cable 12D.
 
Remarks: D means practical external diameter of the cable.

Table1-1, Type Description & Application Occasion of XLPE Insulated Power Cable.
 

Description
Application   Occasion GB China Type
Cu Al
XLPE Insulated PVC Sheath Power Cable To be laid indoors,in tunnel,cable pipeline,the cable couldn't bear mechanical force outside. YJV YJLV
XLPE Insulated PE Sheath Power Cable YJY YJLY
XLPE Insulated,Steel Tape Armored,PVC Sheathed Power Cable To be laid underground,able to bear a certain positive pressure. YJV22 YJLV22
XLPE Insulated,Steel Tape Armored,PE Sheathed Power Cable YJV23 YJLV23
XLPE Insulated,Non-Magnetic Steel Tape Armored,PVC Sheathed Power Cable YJV62 YJLV62
XLPE Insulated,Thin Steel Wire Armored,PVC Sheathed Power Cable Apply to shafts,water and soil,able to bear the larger positive pressure. YJV32 YJLV32
XLPE Insulated,Non-Magnetic Thick Steel Wire Armored,PVC Sheathed Power Cable YJV72 YJLV72
XLPE Insulated,Thick Steel Wire Armored,PVC Sheathed Power Cable Apply to shafts,underwater and seabed,able to bear the positive pressure and the pull. YJV42 YJLV42
XLPE Insulated,Concentric Conductor,PVC Sheathed Power Cable It is used for power transmission on power lines with voltage rated at 0.6/1 kV and below.It is widely used in petrochemical industry,metallurgy,mines and high-rise buildings,etc. YJV-TP YJLV-TP
XLPE Insulated,Concentric Conductor Steel Tape Armored, PVC Sheathed Power Cable YJV22-TP YJLV22-TP
XLPE Insulated,Metallic Shielded,PVC Sheathed Power Cable It is specially suitable for occasions with precision electronic devices,such as computer center,space & aviation supervision center,intellectual buildings,etc. YJVP2 YJLVP2
XLPE Insulated,Steel Tape Armored,Metallic Shielded,PVC Sheathed Power Cable YJV22P2 YJLV22P2
XLPE Insulated,PVC Sheathed,Fire-Proof Power Cable It is used for important occasions with high demand on fire-resistant performance,such as high-rise building,power station,power plant,mine,chemical industry,subway,etc. NH-YJV /
XLPE Insulated,PVC Sheathed,Steel Tape Armored Fire-Proof Power Cable NH-YJV22 /
XLPE Insulated,PVC Sheathed,Fire-Proof Control Cable NH-KYJV /
XLPE Insulated,PVC Sheathed,Steel Tape Armored Fire-Proof Control Cable NH-KYJV22 /
 
The Mian Technique Function of the Cable
1) Cable Conductor DC Resistance: Table 1-2.
2) Partial Discharge Test: Match the Table 1-3 Request.
3) AC Voltage Test:Match the Table 1-4 Request.

Table 1-2, Biggest DC Resistance of Cable Conductor at 20℃

Nominal Cross Section(mm²)
0.5 0.75 1 1.5 2.5 4 6 10
Cu (Ω/km) Non Tinned 36 24.5 18.1 12.1 7.41 4.61 3.08 1.83
Tinned 36.7 24.8 18.2 12.2 7.56 4.7 3.11 1.84
Al (Ω/km) / / / 18.1 12.1 7.41 4.61 3.08
Nominal Cross Section(mm²) 16 25 35 50 70 95 120 150
Cu (Ω/km) Non Tinned 1.15 0.727 0.524 0.387 0.268 0.193 0.153 0.124
Tinned 1.16 0.734 0.529 0.391 0.27 0.195 0.154 0.126
Al (Ω/km) 1.91 1.2 0.868 0.641 0.443 0.32 0.253 0.206
Nominal Cross Section(mm²) 185 240 300 400 500 630 800 1000
Cu (Ω/km) Non Tinned 0.0991 0.0754 0.0601 0.047 0.0366 0.0283 0.0221 0.0176
Tinned 0.1 0.0762 0.0607 0.0475 0.0369 0.0286 0.0224 0.0177
Al (Ω/km) 0.164 0.125 0.1 0.0778 0.0605 0.0469 0.0367 0.0291
 
 Table 1-3, Test Voltage and Maximum Discharge Capacity of the Cable

Rated Voltage (kV)
3.6/6 6.0/6.0 8.7/10 12.0/20 18/30 21/35 26/35
6.0/10 8.7/15
Test Voltage (kV) 6.23 10.38 15.05 20.76 31.14 36.33 44.98
Max.Discharge Capacity (pC) 10 10 10 10 10 10 10
 
 Table 1-4, AC Voltage Test of Cable

Rated Voltage (kV)
0.6/1 1.8/3 3.6/6 6.0/6 8.7/10 12.0/20 18/30 21/35 26/35
3.6/10 6.0/10 8.7/15
Test Voltage (kV) 3.5 6.5 12.5 21 30.5 42 63 73.5 91
Test Time (min) 5 5 5 5 5 5 5 5 5